You are in: Home C24 Central Battery System

C24 Central Battery System

The C24 bank family provides remote power supply for emergency, signal and beacon lights at 24 Vdc.

C24 - 100M

​​​​​​​

C24 - 300M /  C24 - 300M8

Covers one fire zone

C24i - 300M

Covers one fire zone

Manufactured according to the EN50171 norm

As an innovation, Normalux launches a second generation of central battery systems, known as C24I addressable. These new centrals can control and monitor each item connected to them individually and carry out different actions over them (turn on / off, dim, test, etc).                



Compatible with:

               

C24I Addressable has 8 outputs, improving the C24 models that only had 4. Intelligent control that allows to identify any possible problem and is able to control:

  • The central battery unit itself, as well as the 4 outputs of the standard version
  • The central battery unit itself, the outputs and all the luminaires connected to it individiually in the addressable version.



  • Voltage: 230 V AC +/- 10%
  • Wire cross section: 2.5 mm²
  • Output voltage: 24 V DC +/- 20%
  • Output wire section: 2.5 mm²
  • Ambient temperature: -5ºC to 25ºC
  • Class: I
  • IP: IP30
  • Outputs: 4 (C24-100M and C24-300M) / 8 (C24-300M8 andC24I-300M)
  • Maximum current: 3.5 A per output

 

Dimensions:

  • C24-100M: 340 x 330 x 90 mm
  • C24-300M / C24-300M8: 500 x 400 x 200 mm
  • C24I-300M: 587 x 460 x 187 mm

 

 

Model C24-100M
Batteries 2 x 12 V · 7 Ah 2 x 12 V · 9 Ah
Autonomy 1 h 3 h 8 h 1 h 3 h 8 h
Total power output (W) 88 W 36 W 14 W 115 W 48 W 19 W
Maximum current (A) 3,86 1,70 0,76 4,97 2,19 0,97
Phase monitor imput
Output control 4
Potential freecontacts Si
Function indicator Si
Supply indicator for battery Si
Failure Si
Network supply indicator Si
Battery supply indicator Si
Failure alarm indicator Si
Full discharge indicator Si
Active output indicator Si
Communication via bus Si

 

Model C24-300M / C24-300M8
Batteries 2 x 12 V · 12 Ah 2 x 12 V · 18 Ah 2 x 12 V · 24 Ah
Autonomy 1 h 3 h 8 h 1 h 3 h 8 h 1 h 3 h 8 h
Total power output (W) 154 W 36 W 27 W 234 W 105 W 42 W 314 W 136 W 58 W
Maximum current (A) 6,62 2,92 1,30 9,94 4,39 1,95 13,25 5,85 2,60
Phase monitor imput
Output control C24-300M: 4   /   C24-300M8: 8
Potential free contacts Si
Function indicator Si
Supply indicator for battery Si
Failure Si
Network supply indicator Si
Battery supply indicator Si
Failure alarm indicator Si
Full discharge indicator Si
Active output indicator Si
Communication via bus Si

 

Model C24-I300M
Batteries 2 x 12 V · 7 Ah 2 x 12 V · 9 Ah 2 x 12 V · 12 Ah 2 x 12 V · 18 Ah 2 x 12 V · 24 Ah
Autonomy 1 h 3 h 8 h 1 h 3 h 8 h 1 h 3 h 8 h 1 h 3 h 8 h 1 h 3 h 8 h
Total power output (W) 88 W 36 W 14 W 115 W 48 W 19 W 154 W 66 W 27 W 234 W 105 W 42 W 314 W 136 W 58 W
Maximum current (A) 3,86 1,70 0,76 4,97 2,19 0,97 6,62 2,92 1,30 9,94 4,39 1,95 13,25 5,85 2,60
Phase monitor imput
Output control 8
Potential free contacts Si
Function indicator Si
Supply indicator for battery Si
Failure Si
Network supply indicator Si
Battery supply indicator Si
Failure alarm indicator Si
Full discharge indicator Si
Active output indicator Si
Communication via bus Si

 

Compatible with C24

Emergency lighting

Signalling

Step lighting

Light paths

Not only a power supply


Intelligent central battery systems able to warn about any anomaly in the central itself or in any of the four outputs where emergency lighting and or exit signs are connected.


Functioning 100% guaranteed
Duration tests can be customized in the C24 system, even though they are made periodically by default, as well as real time check ups to ensure the functioning of the system.


null

Customizable charging LEDThe C24 system can control the status of the charging LED of the luminaires connected to each of the four outputs.

Ideal for environments where the charging LED could be a nuisance (hotel or hospital rooms)

Turn on: Ok